OEM Supply Tap Water Residual Chlorine Sensor - Conductivity, TDS, Resistivity sensor CR-102S – JIRS Detail:
| Main Technique Specifciation | |||
| Measuring range | 0-20/200/2000us, 0-20mS,0-200mS, 0-10/100/1000ppm | Body main material | Stainless steel 316L, Titanium alloy |
| Constant | 0.01, 0.1, 1.0, 10.0cm-1 | Electrode structure | Bipolar |
| Temp. Compensation | PT1000, PT100, NTC 10K | Response time | 5sec |
| Temp. Range | 0-60℃ | Connect dimension | 1/2″ NPT thread or flanged |
| Pressure range | 0-0.6mPa | Cable length | 5m or as per request |
| Cable join way | Pin or BNC connector | Installation way | Piping or Submersible |
Wire Connection
White wire: Signal +
Black wire: Signal –
Yellow wire: Temp. +
Red wire: Temp -
Applicaions
Widly used for industrial water,tap water, cooling water,boiler circulation water,pure water etc. conductivity measure
Conductivity/Resistivity Sensor CR-102S
online Conductivity/Resistivity Sensor


Product detail pictures:
Related Product Guide:
We offer fantastic strength in high quality and enhancement,merchandising,income and marketing and procedure for OEM Supply Tap Water Residual Chlorine Sensor - Conductivity, TDS, Resistivity sensor CR-102S – JIRS , The product will supply to all over the world, such as: Bolivia, Saudi Arabia, Jamaica, We expect to provide products and services to more users in global aftermarket markets; we launched our global branding strategy by providing our excellent products all over the world by virtue of our well reputed partners letting global users keep pace with technology innovation and achievements with us.